Mounting of Display
Module

Protective Enclosure

A suitable enclosure should be used to protect the rear surfaces of the
Display Module from atmospheric contaminants such as oil, moisture,
dust and corrosive vapors plus other harmful airborne substances. The
Display Module’s gasketed front panel interface to the protective
enclosure is rated as an IP65 degree of protection [National Electrical
Manufacturer’s Association (NEMA)/Underwriters Laboratories (UL)
508, Type 4 (Indoor)] per International Standard IEC 529.

Installation and Orientation

The Display Module can be oriented in any position. The most typical
orientation is shown in Figure 1. The Display Module is designed to fit
into a protective enclosure cutout that has a minimum depth of 50 mm
(2.0 in.) behind the mounting panel. The recommended Display
Module mounting hole pattern and dimensions are defined in
Figure 2. Ensure that the gasket provided is not contaminated with
foreign matter and is installed in the Display Module correctly. Install
the Display Module into the protective enclosure’s front panel using
four M4 nut/lock washer assemblies as shown in Figure 2. Tighten the
M4 nut/lock washer assemblies to 0.9 to 1.1 Nm (8 to 10 lb-in).

Failure to comply with these mounting requirements
may cause damage to the Display Module or
compromise the IP65 [NEMA/UL 508, Type 4
(INDOOR)] degree of protection per International
Standard IEC 529.