Figure 1 Display Module Dimensions

Powermonitor 3000

85.73

(3.375)

85.73

(3.375)

20.64

(0.813)

20.64

(0.813)

22.8

(0.898)

16.0

(0.630)

Shoulder of

Mounting Stud

20.74

(0.816)

9.82

(0.387)

127.00

(5.00)

127.00

(5.00)

Figure 2 Display Module Panel Cutouts and Mounting Sequence

85.73±0.25

(3.375±0.010)

85.73±0.25

(3.375±0.010)

42.88±0.25

(1.688±0.010)

42.88±0.25

(1.688±0.010)

4.78±0.12

(0.188±0.005)

4 Mounting Holes

101.60

+1.52

-0.76

(

4.000

+0.060

-0.030

)

Cutout

Preferred Mounting Panel

Cutout Dimensions

For Bulletin 1404

Powermonitor 3000 Display Module

Mounting the
Bulletin 1404

Powermonitor 3000 Display Module

to the Panel.

Display Module

Gasket

Protective Enclosure Front Panel

(Up to 6.35 mm (0.25 in) Max. Thickness)

Flat Washer

Qty. 4

M4 Nut/Lockwasher Assembly

Qty. 4

Torque to 0.9 to 1.1 Nm (8 to 10 In-Lbs)

Wiring of Display Module

The Master Module powers the Display Module. See Figure 3 for
wiring connections.

Use supplied Allen-Bradley Replacement DM cable Part #
W40863-850-01 or equivalent category 5, shielded, with 4 twisted-pair,
straight-through (not crossed).

Recommended maximum cable length: 3m (10 ft).