58 Powermonitor 3000 Master Module

Publication 1404-IN007F-EN-P - November 2009

Technical Specifications - 1404-M4, 1404-M5, 1404-M6, 1404-M8

Attribute

1404-M4, 1404-M5, 1404-M6,
1404-M8

Dielectric withstand

Control power

2000V

Voltage inputs

2000V

Current inputs

2000V

Status inputs

500V

Control relays

1600V

Terminal blocks

Power supply and voltage input
terminals

4 mm

2

(12 AWG) max,

1.02 N•m (9 lb•in) torque,
75 °C (167 °F) or higher copper
wire only

Relay, KYZ outputs, current input

terminals

(1)

(1)

Recommended ring lug: AMP part # 320634.

2.5 mm

2

(14 AWG) max,

1.18 N•m (10.4 lb•in) torque,
75 °C (167 °F) or higher copper
wire only

Status inputs, RS485

2.5 mm

2

(14 AWG) max,

0.56 N•m (5 lb•in) torque

RIO, DNT (when present)

2.5 mm

2

(14 AWG) max,

0.56 N•m (5 lb•in) torque

Temperature, operating

-20…60 °C (-40…140 °F) cat. no. 1404-DM, 1404-Mxxxx-000,
1404-Mxxxx-DNT
0…55 °C (32 …131 °F) cat. no. 1404-Mxxxx-232, -RIO, -ENT, -CNT

Temperature, storage

-40…85 °C (-40…185 °F)

Humidity

5…95%, noncondensing

Vibration

10…500 Hz: 2 g operational (±0.012 in.)

Shock

1/2 sine pulse, 11 ms duration: 30 g operational and nonoperational

Advertising