11 POINT I/O PROFIBUS Adapter

Publication 1734-IN014C-EN-P - March 2002

Indication

Probable Cause

Adapter Status

Off

No power supplied.
Hardware check in progress.
Initialization in progress.

Green

Operating normally

Red

Hardware check fault.

PROFIBUS Status

Off

No power supplied.
Bus is off-line.

Green

Bus is online (data exchange).

Flashing Green

Adapter has received a CLEAR command from the master.

Red

Error in PROFIBUS initialization.
No modules installed in the backplane.

Flashing Red

1Hz - Check_Configuration telegram rejected.
- Maximum number of POINT I/O modules in master
configuration overridden.
2Hz - SetPrm telegram rejected.
- The first byte in user parameter data does not equal zero.
- Maximum number of user parameter bytes overridden.

PointBus Status

Off

No power supplied.
Hardware check in progress.
Initialization in progress.

Green

Normal operation.

Flashing Red

1Hz -
Incorrect POINT I/O module installed.
POINT I/O module removed from backplane.

Red

Critical link failure (BUS_OFF).