Rockwell Automation 1734-APB POINT I/O Profibus Adapter Module Installation Instructions User Manual

Page 13

Advertising
background image

13 POINT I/O PROFIBUS Adapter

Publication 1734-IN014C-EN-P - March 2002

Interruption

Output voltage will stay within specifications
when input drops out for 10ms at 10V with
maximum load.

General Specifications

Indicators

3 red/green status indicators
Adapter status
PROFIBUS status
PointBus status
2 green power supply status indicators:
System Power (PointBus 5V power)
Field Power (24V from field supply)

Power Consumption

8.1W maximum @ 28.8V dc

Power Dissipation

2.8W maximum @ 28.8V

Thermal Dissipation

9.5 BTU/hr maximum @ 28.8V dc

Isolation Voltage

1250V rms/V ac

Field Power Bus

Nominal Voltage
Supply Voltage Range
Supply Current

24V dc
10-28.8V dc range,
10A maximum

Dimensions Inches

(Millimeters)

3.0H x 2.16W x 5.25L
(76.2H x 54.9W x 133.4L)

Environmental Conditions

Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal
Shock):
-20 to 55°C (-4 to 131°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged
Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged
Nonoperating Thermal Shock):
-40 to 85°C (-40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged
Nonoperating
Damp Heat):
5 to 95% noncondensing

Shock

Operating

Non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30g peak acceleration
50g peak acceleration

Vibration

IEC 60068-2-6, (Test Fc, Operating)
Tested 5g @ 10-500Hz

Advertising