10 ArmorPoint 24V dc Input Modules, Series A

ArmorPoint Digital Input Modules

Input Delay Time, ON to OFF

0.5 ms hardware + (0-63 ms selectable

1

)

Input Point Density

2, 4, or 8

Field Power Bus Supply

Voltage Range,

Nominal


10-28.8V dc

24V dc

Keyswitch Position

1

General Specifications

LED Indicators

2, 4, or 8 yellow input status, logic side

1 green/red network status, logic side

1 green/red module status, logic side

PointBus Current, Maximum

75 mA @ 5V dc

Power Dissipation, Maximum

1738-IB2 - 0.7W @ 28.8V dc

1738-IB4 and -IV4 - 1.0W @ 28.8V dc

1738-IB8 and -IV8 - 1.6W @ 28.8V dc

Thermal Dissipation, Maximum

1738-IB2 - 2.4 BTU/hr. @ 28.8V dc

1738-IB4 and -IV4 - 3.4 BTU/hr. @ 28.8V dc

1738-IB8 and -IV8 - 5.5 BTU/hr. @ 28.8V dc

Isolation Voltage

(continuous-voltage withstand rating)

50V rms

Tested at 1250V ac rms for 60s

Dimensions (includes I/O module

Inches

and mounting base)

(Millimeters)

4.72H x 2.83W x 1.65D

(120H x 72W x 42D)

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20 to 60°C (-4 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

-40 to 85°C (-40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):

5-95% non-condensing

Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):

Operating 30g

Non-operating 50g

Vibration

IEC60068-2-6 (Test Fc, Operating):

5g @ 10-500Hz

ESD Immunity

IEC 61000-4-2:

6kV contact discharges

8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz

10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz

EFT/B Immunity

IEC 61000-4-4:

±3kV at 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:

±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

Conducted RF Immunity

IEC 61000-4-6:

10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz