Publication 1738-IN002B-EN-E - November 2004

ArmorPoint 24V dc Input Modules, Series A 9

Specifications

Following are specifications for the 1738 ArmorPoint digital input
modules.

Indication

Probable Cause

Network Status

Off

Device is not on line:

- Device has not completed dup_MAC_ID test.

- Device not powered - check module status indicator.

Flashing Green

Device is on line but has no connections in the established state.

Green

Device is on line and has connections in the established state.

Flashing Red

One or more I/O connections in timed-out state.

Red

Critical link failure - failed communication device. Device
detected error that prevents it from communicating on the
network.

Flashing Red/Green

Communication faulted device - the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identity Communication
Faulted Request - long protocol message.

Indication

Probable Cause

I/O Status

Off

Input is in the off state

Yellow

Input on

ArmorPoint Digital Input Modules

Inputs per Module

1738-IB2 - 2 (1 group of 2) nonisolated, sinking

1738-IB4 - 4 (1 group of 4) nonisolated, sinking

1738-IV4 - 4 (1 group of 4) nonisolated, sourcing

1738-IB8 - 8 (1 group of 8) nonisolated, sinking

1738-IV8 - 8 (1 group of 8) nonisolated, sourcing

Voltage, Off-State Input, Maximum

5V dc

Voltage, On-State Input,

Maximum

Minimum

Nominal


28.8V dc

10V dc

24V dc

Current, Off-State Input, Maximum

1.5 mA

Current, On-State Input,

Maximum

Minimum

Nominal


5 mA

2 mA

4 mA @ 24V dc

Input Impedance,

Maximum

Nominal


4.7 k

3.6 k

Input Delay Time OFF to ON

0.5 ms hardware + (0-63 ms selectable

1

)