16 POINT I/O 8 Channel High Density Current Input Modules

Publication

1734-IN033B-EN-P - November 2010

Network
status

Off

Device is not on-line
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator

Flashing green

Device is on-line but has no connections in the established
state.

Green

Device on-line and has connections in the established
state.

Flashing red

One or more I/O connections in timed-out state

Red

Critical link failure - failed communication device. Device
detected error that prevents it communicating on the
network.

Flashing
red/green

Communication faulted device - the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identify
Communication Faulted Request - long protocol message.

Channel
status

Off

Module in CAL mode

Solid green

Normal (channel scanning inputs)

Flashing green

Channel being calibrated

Solid red

No power or major channel fault

Flashing red

Channel at end of range (0 mA or 21 mA)

Indicator State

Description