POINT I/O 8 Channel High Density Current Input Modules

21

Publication

1734-IN033B-EN-P - November 2010

EFT/B immunity

IEC 61000-4-4:
±3 kV at 5 kHz on power ports
±3 kV at 5 kHz on signal ports

Surge transient
immunity

IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±2 kV line-earth(CM) on shielded ports

Conducted RF immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications

Certification (when
product is marked)

(1)

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and

Canada. See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous

Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS

CISPR11; Industrial Emissions

Ex

European Union 94/9/EC ATEX Directive, compliant with:

EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
EN 60079-0; General Requirements
II 3 G Ex nA IIC T4 X

(1)

See the Product Certification link at

http://www.ab.com

for Declaration of Conformity, Certificates, and

other certification details.

Environmental Specifications

Attribute

Value

Advertising