Rockwell Automation 1746-NT4 SLC 500 Thermocouple/mV Input Module Installation Instructions User Manual

Page 21

Advertising
background image

SLC™ 500 4-Channel Thermocouple/mV Input Module 21

Publication 1746-IN010D-EN-P - June 2004

Thermocouple Temperature and Millivolt Input Ranges

Input Specifications

Input Type

Temperature Range

Thermocouple Type J

-210°C to +760°C (-346°F to +1400°F)

Thermocouple Type K

-270°C to +1370°C (-454°F to +2498°F)

Thermocouple Type T

-270°C to +400°C (-454°F to +752°F)

Thermocouple Type E

-270°C to +1000°C (-454°F to +1832°F)

Thermocouple Type R

0°C to +1768°C (+32°F to +3214°F)

Thermocouple Type S

0°C to +1768°C (+32°F to +3214°F)

Thermocouple Type B

+300°C to +1820°C (+572°F to +3308°F)

Thermocouple Type N

0°C to +1300°C (+32°F to +2372°F)

Millivolt Input: -50 mV dc to +50 mV dc

Millivolt Input: -100 mV dc to +100 mV dc

Thermocouple Linearization

IPTS-68 standard, NBS MN-125, NBS MN-161

Cold-Junction Compensation

Accuracy ±1.5°C, 0°C to +85°C (+32°F to +185°F)

Input Impedance

Greater than 10M

Temperature Scale (Selectable)

°C or °F and 0.1°C or 0.1°F

DC Millivolt Scale (Selectable)

0.1 mV or 0.01 mV

Open Circuit Detection Leakage Current 12 nA maximum

Open Circuit Detection Method

Upscale

Module Update Time

The sum of all enabled channel’s sample times plus one CJC
update time. See channel sampling time table on page 22.

Channel Turn-On Time,
Reconfiguration Time

Requires up to one module update time plus one of the following:

• 250 Hz Filter = 82 milliseconds
• 60 Hz Filter = 196 milliseconds
• 50 Hz Filter = 226 milliseconds
• 10 Hz Filter = 946 milliseconds

Channel Turn-Off Time

Requires up to one module update time

Time to Detect Open Circuit

500 msec or 1 module update time, whichever is greater