Wiring

Preliminary Considerations

Use the following guidelines in planning the system wiring for the analog modules:

Use Belden cable #8761 for wiring the analog modules making sure that the
drain wire and foil shield are properly earth grounded.

Route the Belden cable separate from any other wiring. Additional noise
immunity can be obtained by routing the cables in grounded conduit.

Ensure that the field wiring crosses AC or power cables at a right angle.

All analog common terminals (ANL COM) are electrically connected inside
the module. ANL COM is not connected to earth ground inside the module.

Voltage outputs are referenced to ANL COM. Load resistance for a voltage
output channel must be greater than or equal to 1K ohms.

Current output channels source current that returns to ANL COM. Load
resistance for a current output channel must remain between 0 and 500
ohms.

ATTENTION

!

Before wiring any analog module, disconnect power from the
SLC 500 system and from any other source to the analog
module.