Wiring the 1734-485asc module, Nc sg s+ s- nc cg, Rx+ rx- nc sg tx+ tx- nc cg – Rockwell Automation 1734-485ASC POINT I/O RS-232 and RS-485 ASCII Modules Installation Instructions User Manual

Page 10

Advertising
background image

10 POINT I/O RS-232 and RS-485 ASCII Modules

Publication

1734-IN588B-EN-P - July 2003

Wiring the 1734-485ASC Module

Module Terminations

Terminal

RS-232

RS-485

RS-422

0

Tx

1

S+

1

Tx+

1

1

Rx

2

NC

Rx+

1

2

NC

S-

2

Tx-

2

3

NC

NC

Rx-

2

4

NC

NC

NC

5

NC

NC

NC

6

NC

CG

CG

7

SG

SG

SC

1 S+ and Tx+ are transmit from the module
2 S- and Rx- are receive into the module

NC

NC

NC

SG

S+

S-

NC

CG

Module

Status

Network

Status

S+ = Transmit

S- = Receive

CG = Chassis Ground

NC = No Connection

SG = Signal Ground

Shielded Cable: The 1734-485ASC module requires
shielded cable to help reduce the effects of electrical
noise coupling. Ground each shield at one end only. A
shield grounded at both ends forms a ground loop, which
can cause module communications to fault. Never connect
a shield to the common side of a logic circuit (this would
introduce noise into the logic circuit).
Connect the shield directly to a chassis ground. This
chassis ground connection is not available on the
1734-485ASC RTB (Removable Terminal Block). On a
POINT I/O system, the chassis ground connection can be
made at the DIN Rail, at the metal panel the DIN Rail is
mounted to, or at the user’s I/O device.

Rx+

Rx-

NC

SG

Tx+

Tx-

NC

CG

Tx = Transmit

Rx = Receive

CG = Chassis Ground

NC = No Connection

SG = Signal Ground

Module

Status

Network

Status

RS-485

RS-422

43487

43487