Specifications - 1734-232ASC, -485ASC Modules (Continued)

Conducted RF Immunity

IEC 61000-4-6:

10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz

Emissions

CISPR 11

Group 1, Class A

Enclosure Type Rating

None (open-style)

Conductors Wire Size

14 AWG (2.5mm

2

) - 22AWG (0.25mm

2

) shielded solid or

stranded copper wire rated at 75

°C or greater

3/64 inch (1.2mm) insulation

Category

2

1

RS-232 Field Wiring Terminations

0 - Tx

1 - Rx

2 - NC

3 - NC

4 - NC

5 - NC

6 - NC

7 - SG

RS-485 Field Wiring Terminations

0 - S+

1 - NC

2 - S-

3 - NC

4 - NC

5 - NC

6 - CG

7 - SG

RS-422 Field Wiring Terminations

0 - Tx+

1 - Rx+

2 - Tx-

3 - Rx-

4 - NC

5 - NC

6 - CG

7 - SG

Terminal Base Screw Torque

7 pound-inches (0.6Nm) maximum

Mass

1.22 oz/34.6 grams

Certifications (when product is
marked)

CE

2

- European Union 89/335/EEC EMC Directive,

compliant with:

EN 61000-6-4; Industrial Emissions

EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

C-Tick

2

- Australian Radiocommunications Act

compliant with AS/NZS 2064, Industrial Emissions

1

Use this conductor category information for planning conductor routing as described in publication
1770-4.1, “Industrial Automation Wiring and Grounding Guidelines.”

2

See the Product Certification link at www.ab.com for Declaration of Conformity, Certificates, and
other certification details.