Troubleshoot with the indicators, Interpret led indicators – Rockwell Automation 1738-IB4DM12 ArmorPoint 24V dc 4-channel Digital Input Module with Diagnostics I.I. User Manual

Page 9

Advertising
background image

Publication 1738-IN021A-EN-E - January 2007

ArmorPoint 24V dc 4-channel Digital Input Module with Diagnostics 9

Troubleshoot With

the Indicators

Interpret LED Indicators

0

1

2

3

MOD

NET

1738-IB4DM12

24V dc In with

Diagnostics

0

1

2

3

IO Diagnostics:

Solid Red = Short

Flashing Red = Open

Module Status Indicators

43680

1738-IB4DM12

Network Status Indicators

I/O Status Indicators

Indication

Probable Cause

Recommended Action

Module Status

Off

No power applied to device

Apply power to device.

Green

Device operating normally

None.

Flashing Green

Device needs commissioning due to configuration
missing, incomplete or incorrect.

Configure device properly.

Flashing Red

Recoverable fault

1. Cycle power to device.
2. If condition persists, replace device.

Red

Unrecoverable fault - may require device
replacement

Replace device.

Flashing Red/Green

Device is in self-test

None.

Network Status

Off

Device is not on line:

- Device has not completed dup_MAC_ID test.

- Device not powered - check module status
indicator.

Apply power to device, wait for
dup_MAC_id to complete, and correct, as
needed.

Flashing Green

Device is on line but has no connections in the
established state.

None - device is in Idle or Program mode.

Green

Device is on line and has connections in the
established state.

None.

Flashing Red

One or more I/O connections in timed-out state.

Check for I/O module failure, and correct, as
needed.