Step: 13 Troubleshooting

The module and SLC provide three aids for troubleshooting:

one status LED on the module

axis error flags returned from the module in the input image table

SLC processor’s fault indication in the status file

When the module or SLC processor detects these types of errors or faults, it
responds accordingly, and you must clear the error or fault as follows:

Module status LED

When this indicator turns ON, if cycling power does not reset the module, return it
the factory for repair or replacement.

When indicated by:

This type of error or fault:

may be cleared by

module status LED

major fault in configuration or
module hardware/firmware

correcting the fault condition and
cycling power to the module

axis error-code words in
the SLC input image table

your data-entry error in the
axis-control structure
(parameter out of range)

re-downloading valid parameters

error code in the
SLC status file

processor fault

correcting the fault condition and
cycling power to the processor