DeviceNet ArmorBlock Network Powered 16-input Module, Series A 17

Publication

1732D-IN012A-EN-E - May 2009

Environmental Specifications

Attribute

Value

Temperature,
operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…60 °C (-4…140 °F)

Temperature,
non-operating

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock):

-45…85 °C (-49…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Un-packaged Damp Heat):

5…95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock,
non-operating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CSPR 11:

Group 1, Class A

ESD immunity

IEC 61000-4-2:

8 kV contact discharges

8 kV air discharges

Radiated RF
immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

1V/m with 1 kHz line-wave 80% AM from 2000…2700 MHz