How to get the related user manual, Determine the module’s chassis power requirement, Choose a module slot in a local i/o chassis – Rockwell Automation 1746-BTM Barrel Temperature Control Module Installation Instructions User Manual

Page 4: Installation considerations

Advertising
background image

4 Barrel Temperature Control Module

Publication 1746-IN020B-EN-P - July 2002

How to Get the Related User Manual

The following table describes the related user manual that is available for this module. To
order a copy or to view or download an online version, visit The Automation Bookstore at:
www.theautomationbookstore.com

Determine the Module’s Chassis Power Requirement

When computing power supply requirements, add the values shown below to the
requirements of all other modules in the SLC

®

chassis to prevent overloading the chassis

power supply:

Choose a Module Slot in a Local I/O Chassis

Place your module in any slot of an SLC 500

TM

module, or modular expansion chassis, except

for the left–most slot (slot 0), reserved for the SLC processor or adapter modules.

Installation Considerations

Most thermocouple–type applications require an industrial enclosure to reduce the effects of
electrical interference. Thermocouple inputs are highly susceptible to electrical noises due to
the small signal amplitudes (microvolt/C°). Isolate them from other input wiring and
modules that radiate electrical interference.
Group your modules within the I/O chassis to minimize adverse effects from radiated
electrical noise and heat. Consider the following conditions when selecting a slot location.
Position the module away from modules that:

connect to sources of electrical noise such as relays and ac motor drives

generate significant heat, such as 32–point I/O modules

For information about:

See this document:

Publication number:

Programming, calibrating and
troubleshooting the barrel
temperature module

Barrel Temperature Control Module
User Manual

1746-UM010

5V dc amps

24V dc amps

0.110

0.085

IMPORTANT

For proper operation, use this module with a local processor. The
module is not designed to operate in a remote chassis.

Advertising