POINTBlock dc 8 Input/8 Output Module 5

Publication 1734-IN020A-EN-P - July 2001

Output Wiring

Note: When connecting more than 1 wire in a termination point, make sure
that both wires are the same gauge and type.

Outputs are electronically protected to 0.75A. Module outputs are
selectable for latched mode or auto-reset mode. (Latched/auto reset is set
by module, not by individual channel.) Each channel is assigned a bit in the
data table to indicate the faulted condition. Outputs in the latched mode can
only be reset with a user command to the module.

Output Terminal

Common Terminal

Power

Remote Termination Block 3

Channel 0

0

4

Channel 1

1

5

Channel 2

2

6

Channel 3

3

7

Remote Termination Block 4

Channel 4

0

4

Channel 5

1

5

Channel 6

2

6

Channel 7

3

7

Module power is supplied from the internal power bus.

Out 0 Out 1

Out 3

Out 2

C

C

C

C

Load

Load

42015

Load

Load

V = 12/24V dc, C = Common

Field power is supplied from internal power bus

0

2

6

3

1

7

4

5

RTB3 shown