Specifications – Rockwell Automation 1738-485ASCM12 ArmorPoint I/O RS-485 ASCII Module, Series A User Manual

Page 10

Advertising
background image

Publication 1738-IN010A-EN-E - June 2004

10 ArmorPoint I/O RS-485 ASCII Module, Series A

Specifications

Following are specifications for the 1738 ArmorPoint ASCII module.

ArmorPoint 1738-485ASCM12 Module
Inputs per Module

1 full duplex

Input Voltage


Some RS-422 and RS-485 equipment use “+” and
“-” descriptors. The “-” corresponds to “A” and the
“+” corresponds to “B”.


“0”, Asserted, ON, Space, Active

“1”, Disasserted, OFF, Mark, Inactive

Threshold Voltages

Signal A with respect to Signal B

RS-422

RS-485

+2 to +6V dc (Transmitter)

+1.5 to +6V dc (Transmitter)

+0.2 to +7V dc (Receiver)

+0.2 to +12V dc (Receiver)


-2 to -6V dc (Transmitter)

-1.5 to -6V dc (Transmitter)

-0.2 to -7V dc (Receiver)

-0.2 to -7V dc (Receiver)

Indicators

1 green/red module status indicator, logic side

1 green/red network status indicator, logic side

2 green TXD, RXD status indicator, logic side

Keyswitch Position

2 (specialty)

PointBus Current, Maximum

75 mA @ 5V dc

Power Dissipation, Maximum

0.75 W @ 28.8V dc

Thermal Dissipation, Maximum

2.5 BTU/hr. @ 28.8V dc

Isolation Voltage

(continuous-voltage withstand rating)

50V rms

Tested at 1250V ac rms for 60s

External dc Power

Supply Voltage

Voltage Range

Supply Current


24V dc nominal

10-28.8V dc

15 mA @ 24V dc

Fault protected to 28.8V dc

Serial Port Parameters

Serial Character Framing

7N2, 7E1, 7O1, 8N1, 8N2, 8E1, 8O1, 7E2, 7O2

Serial Port Comm Speed

9600, 1200, 2400, 4800, 19.2k, 38.4k

Serial Port Receive from ASCII Device

Maximum Number of Receive Characters

1-128

Receive Record Start Mode

No, exclude, include start delimiter

Receive Start Delimiter

ASCII character

Receive Record End Mode

No, exclude, include start delimiter

Receive End Delimiter

ASCII character