Rockwell Automation 1734-IV4/C Point I/O Source Input Module Installation Instructions User Manual

Page 17

Advertising
background image

POINT I/O Source Input Module 17

Publication 1734-IN052D-EN-E - February 2005

Indication

Probable Cause

Network Status

Off

Device is not on-line
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator

Flashing Green

Device is on-line but has no connections in the established
state.

Green

Device on-line and has connections in the established state.

Flashing Red

One or more I/O connections in timed-out state

Red

Critical link failure - failed communication device. Device
detected error that prevents it communicating on the network.

Flashing Red/
Green

Communication faulted device - the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identify Communication
Faulted Request - long protocol message.

Indication

Probable Cause

I/O Status

Off

Input is in the off-state.

Yellow

Input is in the on-state.