20 POINT I/O Source Input Module

Publication 1734-IN052D-EN-E - February 2005

Specifications - 1734-IV2, -IV4 and -IV8 Source Input Modules

Input Specifications (IEC 3 24V dc Input Compliant)

Inputs per Module

1734-IV2 - 2 (1 group of 2), sourcing
1734-IV4 - 4 (1 group of 4), sourcing

1734-IV8 - 8 (1 groups of 8) sourcing

ON-State Voltage

10V dc minimum

24V dc nominal

28.8V dc maximum

ON-State Current

2mA minimum

4mA nominal @ 24V dc

5mA maximum

OFF-State Voltage

5V dc maximum

OFF-State Current

1.5mA minimum

Input Impedance

4.7K

Ω maximum, 3.6K Ω nominal

Input Filter Time

1

OFF to ON

ON to OFF

0.5 hardware plus 0-63ms (user selectable)
0.5 hardware plus 0-63ms (user selectable)

Indicators

1 green/red network status indicator, logic side

1 green/red module status indicator, logic side
1734-IV2
2 yellow input status indicators, logic side
1734-IV4
4 yellow input status indicators, logic side

1734-IV8
8 yellow input status indicators, logic side

Keyswitch Position

1

General Specifications

Module Location

1734-TB, -TBS Mounting base

Pointbus Current

75mA maximum @ 5V dc

Power Dissipation

1734-IV2 - 0.7W maximum @ 28.8V dc
1734-IV4 - 1.0W maximum @ 28.8V dc

1734-IV8 - 1.6W maximum @ 28.8V dc

Thermal Dissipation

1734-IV2 - 2.4 BTU/hr maximum @ 28.8V dc
1734-IV4 - 3.4 BTU/hr maximum @ 28.8V dc

1734-IV8 - 5.5 BTU/hr maximum @ 28.8V dc

Isolation Voltage
(continuous-voltage withstand
rating )

50V

Tested to withstand 2500V dc for 60s

Field Power Bus

Supply Voltage

Voltage Range
Current Range

24V dc nominal

10-28.8V dc

Dimensions Inches

(Millimeters)

2.21H x 0.47W x 2.97L
(56H x 12W x 75.5L)

Advertising