Rockwell Automation 1734D-1B8XOW8S 8 Input/8 Relay Output Module Installation Instructions User Manual

Page 17

Advertising
background image

POINTBlock dc 8 Input/8 Relay Output Module 17

Publication

1734-IN021C-EN-P - September 2006

Environmental Specifications

Attribute

Value

Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal
Shock) -40…85 °C (-40…185 °F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Shock Operating
Nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g

Vibration

IEC 60068-2-6 (Test Fc, Operating): 5 g @ 10…500 Hz

Conducted RF Immunity

IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from
150 kHz…80 MHz

EFT/B Immunity

IEC 61000-4-4: ±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports
±1 kV at 5 kHz on communication ports

ESD Immunity

IEC 61000-4-2: 4 kV contact discharges
8 kV air discharges

Enclosure Type Rating

None (open-style)

Emissions

CISPR 11:
Group 1, Class A

Radiated RF Immunity

IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80%AM from
30…2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
1 V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz

Surge Transient
Immunity

IEC 61000-4-5:
±2 kV line-earth(CM) on power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±2 kV line-earth(CM) on communication ports

Advertising
This manual is related to the following products: