Specifications

Specifications

ac (24V) Input Module (cat. no. 1771-IN)

Number of Inputs

8

Module Location

1771-I/O Chassis, 1 slot

Nominal Input Voltage

24V ac @ 47-63Hz

Nominal Input Current

7mA @ 12V ac

18mA @ 24V ac

22mA @ 28V ac

Onstate Voltage Range

12V ac to 28V ac

Maximum Offstate Voltage

10.5V ac peak

Maximum Offstate Current

2.8mA ac peak

Input Signal Delay

1

18ms (+10ms), on or off for ac

Isolation Voltage

Tested at 1500V dc for 60s between user and system
No isolation between individual channels

Backplane Current

80mA @ 5V dc

Power Dissipation

5.4W maximum, 0.4W minimum

Thermal Dissipation

18.5 BTU/hr maximum, 1.4 BTU/hr minimum

Environmental Conditions

Operating Temperature

0 to 60°C (32 to 140°F)

Storage Temperature

–40 to 85°C (–40 to 185°F)

Relative Humidity

5 to 95% noncondensing

Vibration

2g @ 10-500Hz

Enclosure Type Rating

None (open-style)

ConductorsWire Size

Category

2

14 to 22AWG (2.0 to 0.34mm

2

) stranded copper wire rated at 75°C

or higher
3/64 inch (1.2mm) insulation maximum
2

Field Wiring Arm

Catalog Number 1771-WA

Field Wiring Arm Screw
Torque

7-9 pound-inches (0.8-1.0Nm)

Keying

between 4 and 6

between 10 and 12

Certifications (when product
is marked)

UL

UL Listed Industrial Control Equipment

CSA CSA Certified Process Control Equipment

1 Input off-to-on filter time is the time from a valid input signal to recognition by the module. Input on-to-off filter

time is time from the input signal dropping below the valid level to recognition by the module.

2 You use this category information for planning conductor routing as described in Allen-Bradley

publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.