Rockwell Automation 1734-EPAC POINT I/O ac Power Supply User Manual

Page 14

Advertising
background image

14 POINT I/O 120/240V ac Expansion Power Supply

Publication

1734-IN017A-EN-P - December 2005

POINTBus Output Current

Horizontal DIN rail mounting -

1.3 A at 5.2V dc

Vertical DIN rail mounting -

1.0 A at 5.2V dc

Input Overvoltage Protection MOV and fuse protected

Interruption

Output voltage will stay within specifications when input
drops out for 10 ms at 85V ac with max load.

Module Location

Between I/O modules in 1734 system

Breaks field power bus

Limitations

Use with POINT I/O adapters only

Power Consumption

15.1 W max @ 264V ac

Power Dissipation

8.4 W max @ 264V ac

Thermal Dissipation

28.7 BTU/hr max @ 264V ac

Isolation Voltage

264V continuous

Tested to withstand 3250V dc for 60 s

Field Power Bus

Supply Voltage

Voltage Range

Supply Current

120…240V ac nom, 50…60 Hz

85…264V ac range

10 A max

Dimensions (HxWxL) Metric

Imperial

76.2 x 25.4 x 133.4 mm

3.00 x 1.00 x 5.25 in.

Environmental Conditions

Temperature, Operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…55 °C (-4…131 °F)

Temperature, Storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):

-40…85 °C (-40…185 °F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating

Damp Heat):

5…95% noncondensing

Shock

Operating

Nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

50 g

Vibration

IEC 60068-2-6, (Test Fc, Operating)

5 g @ 10…500 Hz

Advertising