SLC 500™ Analog Input Module 19

Publication 1746-IN006A-US-P

Input Specifications

Description

Specification

Type of Input (Selectable)

±10V dc
1 to 5V dc
0 to 5V dc
0 to 10V dc
0 to 20 mA
4 to 20 mA
±20 mA
0 to 1 mA

Type of Data (Selectable)

Engineering Units
Scaled-for-PID
Proportional Counts (-32,768 to +32,767 range)
Proportional Counts (User Defined Range, Class 3 only)
1746-NI4 Data Format

Input Impedance

1 M

Voltage Input (maximum)

±

30V between any two signal terminals

Current Input (maximum)

30 mA

Time to Detect Open Circuit

1 module scan

Input Step Response

(1)

( 1 )

Depends on filter selected. Refer to the 1746-NI8 User Manual, publication 1746-6.8.

Input Resolution

1 mV or 1 µA

Display Resolution

1 mV or 1 µA

Overall Module Accuracy
(0°C to +60°C, +32°F to +140°F)

Voltage input types
(±10V dc, 1 to 5V dc, 0 to 5V dc, 0 to 10V dc): ±0.1%
Current Input Types
(0 to 20 mA, 4 to 20 mA, ±20 mA):±0.05%
Current Input Type (0 to 1 mA): ±0.5%

Overall Module Drift

Voltage input type: ±6 ppm/°C
Current Input Type: ±12 ppm/°C