6 SLC 500™ Analog Input Module

Publication 1746-IN006A-US-P

Module Location in Chassis

Modular Chassis Considerations

Place your 1746-NI8 module in any slot of an SLC 500 modular, or modular
expansion chassis, except for the extreme left slot (slot 0) in the first chassis. This slot
is reserved for the processor or adapter modules.

Fixed Expansion Chassis Considerations

IMPORTANT

For applications using the upper limit of the operating
temperature range, the 1746-NI8 module (or multiple modules)
should be placed in the right-most slot(s) of the chassis.

Operating Temperature Range

Temperature

Chassis Location

+0°C to +55°C (+32°F to +131°F)

Any slot except slot 0.

0°C to +60°C (32°F to 140°F)

In right most slot of chassis

IMPORTANT

The 2-slot, SLC 500 fixed I/O expansion chassis (1746-A2)
supports only specific combinations of modules. If you are using
the 1746-NI8 module in a 2-slot expansion chassis with another
SLC I/O or communication module, refer to the 1746-NI8 user
manual to determine whether the combination can be
supported.