Setting the jumpers – Rockwell Automation 1746-HSCE2 Multi-Channel High-Speed Counter Installation Instructions User Manual
Page 7
Advertising
Multi-Channel High-Speed Counter 7
Publication 1746-IN002A-US-P
Setting the Jumpers
Six jumpers are located in a row on the side of the module. Use the jumpers to
select the input voltage for each of the inputs A1, B1, Z1, A2, B2, and Z2. The
settings are shown in the figure below.
The 5V dc settings respond to inputs with a active or high settings between 4.2
and 12 volts. The 24V dc settings respond to inputs with active or high settings
between 10 and 30 volts.
IMPORTANT
For a 12V dc encoder signal, use the 24V dc jumper setting.
!
ATTENTION
If jumpers are not set to match the encoder type, the module
may be damaged.
5V dc
4.2-12V dc
24V dc
10-30V dc
JP6 (Z2)
JP5 (B2)
JP4 (A2)
JP3 (Z1)
JP2 (B1)
JP1 (A1 )
(default)
Jumper Settings
Advertising