12

Publication

1738-IN015C-EN-E - February 2010

PointBus Status Indicator

Refer to the table for a description of the PointBus Status indicator.

PointBus Status Indicator

State

Status

Description

Recommended Action

Off

Off or
Process in
Progress

• No power supplied.
• Hardware check in

progress.

• Initialization in

progress.

Turn the adapter on or wait until the
hardware check or initialization has
finished.

Green

Operating
Normally

The adapter is operating
normally.

None.

Flashing
Red

Incorrect or
Missing
I/O Module

• Incorrect ArmorPoint

I/O module is
installed.

• ArmorPoint I/O

module was
removed from
backplane.

Install the correct ArmorPoint I/O
module.

Red

Critical
Failure

Critical link failure
(BUS_OFF).

Check your physical network and
cycle power.