Mount the adapter and i/o bases – Rockwell Automation 1738-APB ArmorPoint PROFIBUS Adapter, Series A User Manual

Page 6

Advertising
background image

6

Publication

1738-IN015C-EN-E - February 2010

Mount the Adapter and I/O Bases

To mount the ArmorPoint adapter on a wall or panel, use the screw holes
provided in the ArmorPoint adapter.

Drilling Dimensions

To install the mounting base:

1. Layout the required points as shown in the Drilling Dimensions

drawing.

2. Drill the necessary holes for #8 (M4) machine or self-tapping screws.

3. Mount the adapter using #8 (M4) screws.

4. Ground the system using the ground lug connection in the I/O bases.

Note that the ground lug connection is also a mounting hole.

5. Mount the terminating base that was shipped with the adapter as the

last base in the backplane instead of the base that was shipped with
the I/O module.

Adapter

102 mm
(4.02 in)

56 mm
(2.2 in)

46.25 mm
(1.8 in)

51.9 mm
(2.0 in)

20.1 mm
(0.8 in)

51.9 mm
(2.0 in)

51.9 mm
(2.0 in)

20.1 mm
(0.8 in)

43769