Connecting rio link devices, Link wiring – Rockwell Automation 1747-ASB Remote I/O Adapter Module User Manual

Page 11

Advertising
background image

Remote I/O Adapter Module 11

Publication 1747-IN014C-EN-P - January 2003

2. Install the module in slot 0 of the remote chassis by aligning the circuit

board with the chassis card guide.

The 1747-ASB module must be installed only in slot 0 (the left slot) of the
remote chassis. Do not install the 1747-ASB module in the remote expansion
chassis.

3. Slide the module into the chassis until the top and bottom tabs lock into

place. To remove the module, press and hold the release located on each
self-locking tab and slide the module out.

4. Cover all unused slots with the Card Slot Filler, Catalog Number 1746-N2.

Connecting RIO Link Devices

Link Wiring

The modules are connected in a daisy chain configuration on any RIO link. A daisy
chain network is formed by connecting network devices together in a serial manner
using Belden 9463 cable. Belden 9463 cable is the only approved cable for
Allen-Bradley RIO links.

The total number of adapters allowed on the RIO link is:

32 if the scanner and all adapters on the RIO link have extended node
capability

16 if the scanner or any adapter does not have extended node capability

Module Release

Card Guide

Advertising