Performing system start-up, Checking operation – Rockwell Automation 1747-ASB Remote I/O Adapter Module User Manual

Page 17

Advertising
background image

Remote I/O Adapter Module 17

Publication 1747-IN014C-EN-P - January 2003

Performing System Start-up

Follow the steps below:

1. Cycle power one last time in save mode (SW3-8 ON).

2. Remove power from the system.

3. Remove the 1747-ASB module and set SW3-8 to the OFF position (check

mode).

4. Replace the 1747-ASB module in slot 0.

5. Apply power to your system.

Checking Operation

During normal operation (PLC or SLC in Run mode), the 1747-ASB module appears
as shown below.

ATTENTION

!

Never insert, remove, or wire modules with power applied to
the chassis or devices wired to the module.

ADAPTER

Red FAULT
LED is off.

Green COMM
LED is on.

Status display indicates a run condition.