Key the backplane connector – Rockwell Automation 1771-IFE/C INSTL.INSTRUCTIONS ANALOG INPU User Manual

Page 4

Advertising
background image

Analog Input Module

4

Publication 1771Ć5.45 - July 1997

The module has configuration jumpers for determining the input type
(voltage or current) desired for each input. The module is shipped
with the configuration jumpers positioned for voltage mode and
the A/B simulation jumper set for Series C. If you are replacing a
Series A or B 1771-IFE module with this module, reset the
simulation jumper as shown above.

You can select either voltage or current for each input, but all inputs
must be either single-ended or differential. Do not mix single-ended
and differential inputs on the module.

Reposition the configuration jumpers associated with each input

channel according to your requirements

12

You can mix voltage mode and current mode settings on

the module. Make sure that the entire module is set for

either singleĆended or differential. Do not mix them.

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Channel 7

Channel 8

Channel

1 and 2

Channel

3 and 4

Channel

5 and 6

Channel

7 and 8

Channel

9 and 10

Channel

11 and 12

Channel

13 and 14

Channel

15 and 16

Differential

SingleĆended

Voltage Mode

Differential

Current

SingleĆended

Current

Differential or SingleĆended (factory set)

Current Mode

Odd channel current
Even channel voltage

Even channel current
Odd channel voltage

SingleĆended

Configuration

Jumpers

Remove the four screws securing the side cover to

the module and remove the covers.

19805

11

Reposition the cover and secure with the four

screws removed in step 1.

19813

13

Position the keying bands in the backplane connectors

to correspond to the key slots on the module.

Place the keying bands:

between 10 and 12

between 24 and 26

You can change the position of these bands if

subsequent system design and rewiring makes

insertion of a different type of module necessary.

Upper Connector

11022ĆI

I/O chassis

Place your module in any slot in the chassis

except the leftmost slot which is reserved for

processors or adapters.

Key the Backplane Connector

4

Set the Configuration

Jumpers and Key the

Backplane Connector

Advertising