Default Data Map for the Module

1738-OE4CM12

Message size: 4 Bytes

1738-OE4CM12

Message size: 8 Bytes

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Produces
(Scanner
Rx)

High Byte - Channel 1 Status

Low Byte - Channel 0 Status

Not used

H
C
A

L

C
A

C
M

C

F

Not used

H
C
A

L

C
A

C
M

C

F

High Byte - Channel 3 Status

Low Byte - Channel 2 Status

Not used

H
C
A

L

C
A

C
M

C

F

Not used

H
C
A

L

C
A

C
M

C

F

Where:

CF = Channel Fault Status, 0 = no error, 1 = fault

CM = Calibration Mode; 0 = normal, 1 = calibration mode

LCA = Low Clamp Alarm; 0 = no error, 1 = fault

HCA = High Clamp Alarm; 0 = no error, 1 = fault

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Consumes
(Scanner
Tx)

Output Channel 0 High Byte

Output Channel 0 Low Byte

Output Channel 1 High Byte

Output Channel 1 Low Byte

Output Channel 2 High Byte

Output Channel 2 Low Byte

Output Channel 3 High Byte

Output Channel 3 Low Byte