Install a Central Ground Bus
Each enclosure must contain a central ground bus. The ground bus is the common
connection for each chassis within the enclosure and the enclosure itself. If you
have not already installed a central ground bus, see the Industrial Automation
Wiring and Grounding Guidelines, publication 1770-4.1.
Connect Equipment Grounding Conductor
IMPORTANT
Use the following information, along with the installation manual
for your programmable controller, to functionally ground the
chassis.
TIP
Keep wire length as short as possible.
chassis mounting tab
ground lug with 5.2mm
2
(10 AWG) wire
4M or 5M (#10 or #12) phillips screw and
star washer (or SEM screw)
4M or 5M (#10 or #12) star washer