Rockwell Automation 1734-EP24DC Point I/O Expansion Power Supply Installation Instructions User Manual

Page 7

Advertising
background image

POINT I/O 24V dc Expansion Power Supply 7

Publication

1734-IN058B-EN-P - June 2005

ATTENTION

Do not connect 120/240V ac to the 1734-EP24DC
terminals. Damage to the supply will result.

ATTENTION

Use the 1734-EP24DC expansion power supply only with
1734 POINT I/O adapters, such as the 1734-ADN
DeviceNet adapter.

ATTENTION

POINT I/O is grounded through the DIN rail to chassis
ground. Use zinc plated yellow-chromate steel DIN rail to
assure proper grounding. The use of other DIN rail
material (e.g., aluminum, plastic, etc.) that can corrode,
oxidize, or are poor conductors, can result in improper or
intermittent grounding.
Secure DIN rail to mounting surface approximately every
200 mm (7.8 inches).

Advertising