ArmorPoint I/O Modules with 8 Configurable 24V DC Points and DeviceLogix 15

Publication

1738-IN027B-EN-E - February 2010

Configuration of the 1734-8CFGDLX module must be done through
RSNetWorx for DeviceNet.

Data [46]

Peer 7 – EPR (ms)

Data [47]

Where:

Filter = 0...65535

μs (1000 = default)

FltM = Fault Mode (0 = Fault Value (default), 1 = Hold Last State)

FltV = Fault Value (0 = OFF (default), 1 = ON

IdIM = Idle Mode (0 = Idle Value (default), 1 = Hold Last State)

IdIV = Idle Value (0 = OFF (default), 1 = ON)

RACK = Produce with Rack Assembly 4 and Consume Rack Assembly 34

(0 = Disabled (default), 1 = Enabled)

CFO = DeviceLogix Communication Fault Override of Outputs

1 = Enabled. When enabled, the DeviceLogix program will continue to control the
outputs even in the event of a communication fault.

0 = Disabled (default). When disabled, the outputs will follow the Fault and Idle
settings.

DM = Dependent Mode

MP = Masterless Produce

0 = Disabled (default), 1 - Enabled. When enabled, the module will begin
producing data at powerup and after a connection with a controller is
terminated.

EPR = Expected Packet Rate in milliseconds

PIT = Production Inhibit Time in milliseconds

Slot / MacID = Address of peer

Data Map - Configuration Assembly 123