Network status

Off

Device is not online:

- Device has not completed dup_MAC-id test.

- Device not powered – check module status
indicator.

Green

Device is online and has one or more I/O
connections in established state.

Flashing green

Device is online but has no connections in
established state.

Flashing red

One or more I/O connections in timed-out state.

Red

Critical link failure – failed communication
device. Device detected error that prevents it
from communicating on the network.

Flashing red/green

Communication faulted device – the device has
detected a network access error and is in
communication faulted state.

Device has received and accepted an Identity
Communication Faulted Request – long
protocol message.

I/O status

Off

I/O is inactive.

Yellow

I/O is active and under control.

Flashing yellow

I/O is in charging state.