Remove the unit below the feeder unit, Secure the support pans – Rockwell Automation 2100M Feeder Circuit Breaker Units Secure Support Pan and ChangeDoor Latch User Manual

Page 6

Advertising
background image

6

Rockwell Automation Publication 2100-IN091A-EN-P - April 2013

Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch

12. If one of the following units is directly above or below the Feeder/Main

unit, verify that the incoming power source is off and that the operator

handle is in the OFF/O position before you open that unit door:
Main Lug Compartment unit (Bulletin 2191)
Main Disconnect Switch unit (Bulletin 2192M)
Main Circuit Breaker unit (Bulletin 2193M)
Frame mounted unit
Bottom horizontal wireway

Remove the Unit Below the

Feeder Unit

If the unit below the Feeder unit is a plug-in unit, remove that plug-in unit from

the section. Follow

step 1

11

of

Remove the Feeder Unit from the Section

to

remove any additional units from the MCC section.

Secure the Support Pans

Follow these steps to secure the support pans.

1. Secure the left-rear corner of the unit support pan with a 10-32

self-tapping screw and tighten to 32 lb•in (3.6 N•m) by using a 5/16 in.

socket wrench.

IMPORTANT

Add the screw to the Feeder unit support pan and the unit support pan above
the Feeder unit, if one is installed.

TIP

You can use an industrial, battery-powered screwdriver with a strong magnetic

bit. Use a driver bit extension. We recommend placing a cloth near the work
area to catch the screw if it falls from the driver bit. You can use a small pry bar
between the right-hand edge of the unit support pan and the right-hand unit

support to better align the holes on the left-hand edge of the unit support
pan. Inserting these screws can take more than one attempt.

Unit Support Pan

10-32 self-tapping

screw

32 lb•in (3.6 N•m)

Unit Support Pan

Right-hand Unit

Support

Pry Bar

Gently apply pry

bar to align holes.