Install latch angle bracket – Rockwell Automation 2100M Feeder Circuit Breaker Units Secure Support Pan and ChangeDoor Latch User Manual

Page 8

Advertising
background image

8

Rockwell Automation Publication 2100-IN091A-EN-P - April 2013

Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch

Install Latch Angle Bracket

The latch angle bracket installs in the top-right corner of the Feeder unit

compartment. Follow these steps to install the latch angle bracket.

1. Remove the plastic retaining clip from the right-hand unit support pan.
2. Secure the latch angle bracket to the right-hand unit support with a ¼-20

screw and lock washer and tighten to 55 lb•in (6 N•m) with a 3/8 in.

socket wrench.

TIP

The latch angle bracket has two tapped holes, but only one hole is used for
mounting. The tapped hole used depends on where the Feeder unit was

mounted in the section:
If the Feeder unit was mounted directly below the top horizontal wireway

pan, then the bottom tapped hole of the latch angle bracket is used to

mount the bracket to the right-hand unit support.

Otherwise, use the top tapped hole of the latch angle bracket.

Latch Angle

Bracket

¼-20 Screw and

Lock Washer

55 lb•in (6 N•m)

Latch Angle

Bracket

Mounting Holes

Advertising
This manual is related to the following products: