Specifications, Instance 102 - configuration input / output, Input – Rockwell Automation 1799ER-IQ10XOQ10 Dual-Port EtherNet Embedded I/O Board with 10 Inputs/ Outputs User Manual

Page 16: Output

Advertising
background image

16 Dual-Port EtherNet Embedded I/O Board with 10 Inputs/ 10 Outputs

Publication 1799ER-IN001B-EN-P - May 2013

Specifications

5

Group 0 Input OFF_ON Delay Filter (High Byte)

6

Group 0 Input ON_OFF Delay Filter (Low Byte)

7

Group 0 Input ON_OFF Delay Filter (High Byte)

8

Reserved

IV_G0

IA_G0

FV_G0

FA_G0

9

Reserved (pad)

CRN = Configuration Revision Number. Value is 0 after power-on reset and after completely closing the
connection. Value is 1 when the module is configured. Once a module is configured, the only way to
change its configuration is to close the connections to it or use the override value of 0.
FA_Gx = Fault Action Group x. 0 = Apply Fault Value, 1 = Hold Last State
IA_Gx = Idle Action Group x. 0 = Apply Idle Value, 1 = Hold Last State
FV_Gx = Fault Value Group x. 0= Off, 1=On
IV_Gx = Idle Value Group x. 0= Off, 1=On
Input Filter values = 0, 1000, 2000, 4000, 8000, or 16000 microseconds.

Input

Attribute

Value

Inputs per block

10 sinking or sourcing, Type 1 + compatible

Off-state voltage

5V DC max

Off-state current

1.5 mA max

On-state voltage

10...30V DC

On-state current

2...11 mA

Output

Attribute

Value

Outputs per block

10 sinking or sourcing, 0.5A, short circuit protected, pilot duty

Output auxiliary voltage

10...30V DC

On-state voltage drop

250 mV max

Instance 102 - Configuration Input / Output

Config Byte Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0