Rockwell Automation 1797-TCAP ControlNet Ex Tap Dummy Load Installation User Manual

Page 4

Advertising
background image

4

ControlNet Ex Tap Terminator Installation Instructions

1797-5.30 - September 1999

Certified Equivalent ControlNet Ex System Diagram Items

You may use these items as equivalents for the items shown on the system

diagram.

ControlNet Ex
Tap

1797-TPx

ControlNet Ex Coax
Tap

Four types of connections
available: S (straight t-tap), R
(right angle t-tap), YS (straight
y-tap), and YR (right angle
y-tap) - a maximum of 48
taps can be connected
together by coax trunk cable

CNet Ex Trk Trm 1797-XT

ControlNet Ex Trunk
Terminator

Simple resistor (75

) with

coax connector that must be
on each end of the ControlNet
Ex coax trunk for termination

Coax Trunk
Cable

1797-RG6

Quad-Shield, RG-6
75

Coax Trunk

Cable

Maximum (functional) length
between 2 1797-TPx is
3280ft (1000m) - each
1797-TPx reduces the
(functional) coax cable length
by 53.4ft (16.3m)

None

None

Standard Coax Trunk
Cable BNC Couplers

Different standard cable
couplers, 90

o

, 180

o

, etc.

System Diagram Name

Catalog Number

Source

Coax Trunk Cable

1797-RG6

Allen-Bradley

3092A

1

Belden Wire & Cable Co.

3092A with blue jacket

Belden Wire & Cable Co.

1

Belden Wire & Cable 1189A may be used, but with functional loss of communication
distance and/or nodes.

System
Diagram Name

Catalog
Number

Catalog Name

Description

Advertising