Required Tools

These tools are required for computer installation:

#2 cross-head screwdriver
Panel cutout tools (for panel mounting)
Drill motor and drill bit (for wall, machine, and table mounting)
Antistatic wrist strap

Install the Computer

The computers support the following mounting options:

Panel mount (display computer models)
Wall, machine, table, and bookshelf mounts (non-display computer models)

Panel Mounting Guidelines

Observe these guidelines when installing the computer in a panel:

Remove all electrical power from the panel before making the cutout.
Confirm that there is adequate space behind the panel. For specific

information, refer to

Mounting Clearance Requirements

on

page 24.

Cut supporting panels to specifications before installation. Take precautions

so metal cuttings do not enter components already installed in panel.

Supporting panels must be at least 14 gauge for proper sealing against water
and dust and to provide proper support. The mounting hardware supplied
accommodates panel thickness between 1.5…5.5 mm (0.06…0.22 in.).

Make sure the area around the panel cutout is clear.
Certain restrictions apply when mounting a display computer in a panel.

See

Figure 14

for details.

Figure 14 - Acceptable and Unacceptable Mounting Positions for Display Computers

ATTENTION: Failure to follow these guidelines can result in personal
injury or damage to the panel components.

Acceptable

Unacceptable

In either position, front USB port
must be near bottom of display.

≤60°
from Vertical

≤60°

from Vertical