Maintenance, Safety considerations, Specifications – Rockwell Automation T7441A ICS Regent+Plus DC Digital Output Module 24VDC User Manual

Page 11

Advertising
background image

(T7441A) DC Digital Output Module


P D - 7 0 1 5 M a r - 0 6

11

control logic by using a contact element (or similar element)
with the output point name.

Maintenance

No periodic maintenance or calibration is required for this
module.

Fuses for each output are located within the module. To
replace a blown fuse the output module must be removed from
the I/O chassis and opened. To open the output module,
remove four screws from the side of the module’s clamshell.
Remove the blown fuse from its retaining clips (on the circuit
board) and replace it.

To prevent damage to the module, replacement fuses must be
of the same rating and type (see Specifications, below).

To prevent electrostatic damage to sensitive module circuits,
maintenance personnel should always use the proper anti-
static work areas and grounding straps when handling or
working with circuit boards.

Safety Considerations

The DC digital output module is TÜV certified as non-
interfering, and can be used in a safety system for simplex

non-safety critical outputs. For safety critical outputs,
guarded output modules should be used (model T3461A,
T3481 or T3485 are recommended).

Specifications

Safetybus Power

0.8 load units

Number of Outputs

16 circuits divided into two
groups of 8 circuits each

Voltage Range

18 to 30 VDC

Load Current

2 amps maximum per output
0

°

to 60

°

C

Advertising