Rockwell Automation T7441A ICS Regent+Plus DC Digital Output Module 24VDC User Manual

Page 12

Advertising
background image

DC Digital Output Module (T7441A)


1 2

Industrial Control Services

Minimum Load

0 mA

On State Drop

0.5 volts maximum @ 2 amps

Surge Current

15 amps, 20 msec

Output Leakage

1 mA maximum

Fusing

One 3 A, 250 V, fast-acting
(3AG) per output, located
inside module

Turn-On Delay

1.0 msec, maximum

Turn-Off Delay

1.0 msec, maximum

Heat Dissipation

16 Watts, 54 BTUs/hour

Over voltage Protection

45 VDC, continuous

Isolation

2500 volts minimum (field
wiring to control logic)
2500 volts minimum (output
group 1-8 to output group 9-
16)

Operating Temperature

0

°

to 60

°

C

(32

°

to 140

°

F)

Storage Temperature

-40

°

to 85

°

C

(-40

°

to 185

°

F)

Operating Humidity

0 to 95% relative humidity,
non-condensing

Vibration

10 to 55 Hz:


±0.15mm

Shock

Operating:


15 g, ½ sine wave, 11 msec

Electromagnetic
Interference

IEC 801 Part 2 - Electrostatic

Discharges

IEC 801 Part 3 - Radiated

Electromagnetic Fields


Level 3: Contact discharge of
6 kV
Level 3: 10 V/M, 27 MHz -
500 MHz