Channel Status Indicator (six in all)

Reset Switch

The XM-360, XM-361, and XM-362 modules have an external reset switch on top of the module. The Reset switch can be
used to reset all latched relays in the Relay Expansion module when it is attached to an XM-360, XM-361, or XM-362
module.

Color

State

Description

No color

Off

Normal operation with alarm limits on the channel.
No power applied to the module; look at Module Status indicator.

Yellow

Solid

An alert level alarm condition exists on the channel (and no sensor-out-of-range or danger level alarm condition exists).

Red

Solid

A danger level alarm condition exists on the channel (and no sensor-out-of-range condition exists).

Flashing

A sensor-out-of-range condition exists on the channel.

IMPORTANT

The Reset switch resets the relays only if the input is no longer in alarm or the condition that caused the alarm is
no longer present.