Calculated Industries 5070-A Pocket Reference Guide User Manual

Page 22

Advertising
background image

P

ocket

R

efeRence

G

uide

— 21

(cont’d)

KEYSTROKE

DISPLAY

 

0.

1. Set to 3-Phase:

 

(3Ш)

3 Ph

2. Set to 60º C:

 

(60º)

3Ø 60

3 Ph

3. Set to Copper (if necessary):

 

(Cu/Al)

3Ø 60 Cu

3 Ph

4. Enter Volts:

   

VOLT 230.

5. Enter HP:

  

IND* 10. hP

* Press   until

iND is displayed in the

upper left area of the display.

6. Find Full-Load Current:

FLC

28.

A

7. Find 125% Ampacity Wire Size:

 

(125%)

AWG 8 Cu

WIRE SIZE 125%

amPaCITY WIRe sIZInG

Wire Sizing is based on Ampacity

requirements used in NEC Tables

310.15(B)(16) and 310.15(B)(17).

Wire Sizing

Wiring is being installed for a 240V,

1Ø system rated at 30 kVA. What is

the 60° C Copper Wire Size?