Calculated Industries 5070-A Pocket Reference Guide User Manual

Page 28

Advertising
background image

P

ocket

R

efeRence

G

uide

— 27

(cont’d)

3. Set to Copper (if necessary):

 

(Cu/Al)

75 Cu

3 Ph

4. Enter Amps:

  

AMPS 20.

5. Enter Volts:

   

VOLT 208.

6. Enter Length:

   

FEET 175.

7. Enter allowable VD%:

 

DROP 3.0

%

V

8. Find Wire Size:

AWG 8 Cu

VD WIRE SIZE

Finding Voltage Drop Distance

How far from a Three-Phase 240

Volt source can you install a 15 Amp

load using 60°C #10 Copper branch

circuit conductors? Assume a 3%

allowable Voltage Drop.

KEYSTROKE

DISPLAY

 

0.

1. Set to 3-Phase:

 

(3Ш)

3 Ph

2 Set to 60º C:

 

(60º)

3Ø 60

3 Ph

3. Set to Copper (if necessary):

 

(Cu/Al)

60 Cu

3 Ph