Calculated Industries 5070-B Pocket Reference Guide User Manual

Page 24

Advertising
background image

P

ocket

R

efeRence

G

uide

— 23

(cont’d)

3. Set to Copper (if necessary):

 

(Cu/Al)

3Ø 75 Cu

3 Ph

4. Enter Amps:

   

AMPS 265.

5. Find Wire Size:

AWG 300

Cu

WIRE SIZE

6. Change to Aluminum:

 

(Cu/Al) AWG 400 AL

WIRE SIZE

Sizing Parallel Conductors (Free air)

What size 60°C insulated Copper

Wire is required for a single conductor

carrying a 500 Amp load in a Free

Air environment (30°C Ambient

Temperature.)? What size for two

Parallel conductors?

KEYSTROKE

DISPLAY

 

0.

1. Set to 60º C:

 

(60º)

60

0.

2. Set to Copper (if necessary):

 

(Cu/Al)

60 Cu

0.

3. Set to Free Air mode:

 

(FrAir)

60 Cu FrAir

0.

4. Enter Amps:

   

AMPS 500.

5. Find Wire Size for one conductor:

AWG 500 Cu

WIRE SIZE