finding Motor branch-Circuit Wire size and Conduit size —

Same Wire type and Size

What size THHN Copper Wire and RMC Conduit are needed to

connect a 10 HP 1Ø Induction motor to a 115 Volt source?

KeysTRoKe

DIsPlay

 

0.

1. Set to 1-Phase:

 

(1Ш)

1 Ш

1 Ph

2. Set to 60º C:

 

(60º)

1 Ø 60

1 Ph

3. Set to Copper (if necessary):

 

(Cu/Al)

1 Ø 60 Cu

1Ph

4. Enter Volts:

   

VolT 115.

5. Enter Horsepower:

  

InD* 10. hP

* If

iND is not shown, press   until iND is displayed in the upper left

area of the display.

6. Display Full-Load Amps:

flC 100.

a

7. Find Wire Size at 125% Ampacity:

 

(125%)

aWG 0 Cu

WIRe sIZe 125%

8. Find Wire Ampacity:

Ø* 125.0

WIRe a125%

* The Wire Size will be shown in the upper left area of the display when

displaying the Wire Ampacity rating.

9. Enter Conduit Type and find Conduit Size:

  

(Cond Type)

RMC 1.25 in

ConD sIZe

(cont’d)