finding Conduit size —

Multiple conductors, Different Wire Sizes and types

Three 1/0 THWN 75°C conductors and one #2 XHHW 75°C Copper

conductor are to connect to a panel board using a single Conduit.

What is the cross-sectional area of Wires, Conduit Size and actual

fill Area?
Note: The cross-sectional Areas are the same for both THHN and

THWN; display will show as THHN.

KeysTRoKe

DIsPlay

 

0.

1. Set to 75º C:

 

(75º)

75

0.

2. Set to Copper (if necessary):

 

(Cu/Al)

75 Cu

0.

3. Enter Conduit Type:

  

(Cond Type)

fMC none

ConD

4. Enter first Wire Size:

 

*

aWG 0 Cu

WIRe sIZe

5. Enter number of THWN Wires:

 

Thhn 3.

WIRes

6. Find cross-section Wire Area:

Thhn 0.5565

WIRe aRea

7. Enter second Wire Size:

 

*

aWG 2 Cu

WIRe sIZe

8. Enter number of XHHW Wires:

 

XhhW 1.

WIRe

9. Find cross-sectional Wire Area:

XhhW 0.1146

WIRe aRea